Christmas Eve… another sweltering day in Perth – peaking close to 39.0°

Spending quality time at home with the Family after a massive week 😊

5.51pm, email notification that one of our Major Customers critical Chiller Plants has failed… (BGIS have been running VERIFi in this critical Chiller Plant for over 6 months)

·        Quick remote dial into site via VERIFi platform
·        Review of Trane Chiller via TechView – confirm fault
·        Review of key operational trends via Tridium Niagara N4
·        Verified that it is a struggling cooling tower
·        Limit Front Panel Current Limit Setpoint to 90%
·        Reset alarm via TechView
·        Chiller is ready to run again…

6.21pm, all alarms cleared, customer is notified of job complete & monitoring continues…